Extension Cable Selection Chart
Table A: Maximum Input-Side Cable Extension Length (m)(m)
Applicable Models:HC/H (Inverter Series)
HC111B, HC113B, HC116B, HC230B, H260B
| Cable Size (mm2) | HC111B | HC113B | HC116B | HC230B | H260B |
|---|---|---|---|---|---|
| 3.5 | 25 | 20 | 15 | 60 | 35 |
| 5.5 | 35 | 30 | 25 | 95 | 60 |
| 8.0 | 50 | 45 | 35 | 140 | 85 |
| 14.0 | 90 | 80 | 60 | 250 | 150 |
| 22.0 | 140 | 120 | 95 | 390 | 230 |
Table B: Maximum Output-Side Cable Extension Length (m)
Applicable Models: ICV/HBM (Internal Vibrators) [Per Unit]
| Cable size (mm2) | φ30 | φ40 | φ50 | φ60 | CSV50 |
|---|---|---|---|---|---|
| 3.5 | 100 | 60 | 30 | 20 | 60 |
| 5.5 | 150 | 100 | 60 | 40 | 100 |
| 8.0 | 200 | 140 | 80 | 60 | 140 |
| 14.0 | 400 | 250 | 150 | 100 | 250 |
| 22.0 | 600 | 400 | 200 | 150 | 400 |
Table C: Calculation Formula

- S: Cable size (mm131) [Cross-sectional area]
- L: Cable length (m)
- I: Total current (A) [Rated current of the vibrator × Number of units used]